Controlling BACnet priority levels
Text boxes and the toggle switch elements that control BACnet properties have an information circle next to them. Clicking the information circle opens the BACnet Priority menu. Use the menu to change the priority for writing and relinquishing a value in the priority array.
The Relinquish Default and Out of Service properties are for information only and cannot be changed from the menu.
BACnet Priority menu
The gray or blue information icons changes to orange when a value is entered at a BACnet priority 8 or higher.
The change the BACnet priority for writing, do the following:
|
1
|
Click the information circle next to a text box or toggle switch element. The Priority menu opens. |
|
2
|
From Write at Priority, choose a new priority level. |
|
3
|
When finished, click Close or the close button . The Priority menu will also close when a new value is an entered into a text box. |
New values entered in the text box or toggle switch element will be entered into the priority array at the new level.
To relinquish a priority level, do the following:
|
1
|
Click the information circle next to a text box or toggle switch element. The Priority menu opens. |
|
2
|
Select the check boxes to relinquish a priority level. |
|
3
|
When finished, click Relinquish Selected. |